Split Case Fire Pump

Horizontal Split Case Fire Pump

Horizontal Split Case Fire Pump by RP
Single stage horizontal split case fire pump for firefighting applications. NFPA-20 design. UL Listed and FM Approved.

Operation Limits

Capacity up to 1136 m³/h (5,000 gpm)
Head up to 204 m (670 ft)
Pressure up to 20 bar (290 psi)
Temperature 10° to 105° C (50° to 220° F)
Applications Commercial, municipal and residential high-rise buildings, Large industrial premises and storage warehouses, Offshore and remote facilities, Airports, Power stations.
Base price

Overview

Ruhrpumpen's split case centrifugal fire pumps feature a heavy shaft and short bearing span that reduces shaft deflection to a minimun, providing longer packing and bearing life and lower maintenance costs, while requiring less floor space.

RP's split case fire pumps are built per NFPA 20 standards, and are listed by Underwriters Laboratories (UL) and approved by Factory Mutual (FM).

CHARACTERISTICS
  • Compact design and efficient operation
  • Shaft sleeve to protect the shaft against corrosion and wear
  • Interchangeable radial and thrust bearings with grease lubrication are guaranteed
  • Enclosed, double suction impeller, casted in one-piece and balanced to minimize thrust and ensure longer bearing life
  • Available with electric or diesel drives
DESIGN FEATURES
  • NFPA-20
  • UL-448
  • FM-1311

Special designs available on request

Ruhrpumpen also designs Fire Pump Systems with ABS certification for floating offshore facilities.

CONSTRUCTION MATERIALS

Standard materials include:

  • Cast iron
  • Bronze Fitted

Special materials available on request

FIRE MARKET APPLICATIONS
  • Sprinkler systems
  • Hydrant systems
  • Water curtains


Ruhrpumpen Fire Pumps and Systems Certifications